Can the heat from data centres be used to warm homes?

The claim: “The heat from data centres could warm our homes.”

PARTLY Hum’s verdictEU evidencecompany figures

Short answerYes, in a few places. Across the EU, about 1.8% of it is reused.

Yes, it can, but few do. Practically all the electricity a data centre uses turns into heat. In Odense, Denmark, heat pumps take heat from Meta’s data centre, warm it to 70-75°C and send it into the city’s district heating pipes. The engineers say it heats more than 12,000 homes. A Danish price cap on this kind of heat limited how much the local heat company used, until politicians decided to scrap it. Near Helsinki, Fortum says heat from two Microsoft data centres will start flowing step by step from next year, and once complete should cover about 40% of the 2 TWh a year of district heat used by 250,000 heat users. That’s about 0.8 TWh of heat a year (Hum’s arithmetic). But in the EU’s first reporting round, only 67 of 770 data centres reported reusing any heat, and about 1.8% of all the heat was reused. It needs heat pipes nearby and someone who wants heat, and demand is low in summer and in warm places. EU law now says data centres above 1 MW must use their waste heat unless they show it isn’t technically or economically feasible.

The bigger pictureAll the world’s data centres used about 485 TWh of electricity in 2025, the IEA estimates, and practically all of it ends up as heat. Nobody publishes how much of that is reused worldwide. In the EU, where it is measured, it’s about 1.8%.

Wh is a watt-hour: a 1-watt light left on for an hour. 1 kWh = 1,000 Wh. 1 TWh = 1 billion kWh.

Why the claim misleads

It works, and real homes are heated this way in Odense. But it needs district heating pipes and a cold climate, so most data centres don’t do it: about 1.8% of EU data centres’ heat is reused, and the biggest Nordic scheme hasn’t started taking heat yet.

What nobody knows yet
  • Outside the EU, nobody publishes how much data-centre heat is reused.
  • The EU’s 1.8% may not be representative: some reported values looked unrealistically high, and some countries with known schemes reported none.
  • Only about 36% of the EU data centres that had to report did so in the first round.
  • How much Microsoft heat will reach homes near Helsinki, and when, depends on Microsoft’s building schedule.
Sources (15)

Hum’s sums

  • 40% of 2 TWh a year = 0.8 TWh of heat a year
Cite this

EU Energy Efficiency Directive (EU) 2023/1791, Article 26(6), as quoted in Hum, “Can the heat from data centres be used to warm homes?”, https://humearth.org/q/heat-reuse (quote checked 8 Nov 2026).

Cite the original source first; Hum is where you found it.

What do Wh, kWh and TWh mean?

Wh is a watt-hour: a 1-watt light left on for an hour. 1 kWh = 1,000 Wh, and 1 TWh = 1 billion kWh. Hum compares each number with something everyday so you don’t need the units.

Send this answer

Can data centres heat homes? Yes: in Odense, Denmark, Meta’s heats more than 12,000 homes, the engineers say. But across the EU only about 1.8% of data centres’ heat is reused.