Can the heat from data centres be used to warm homes?
The claim: “The heat from data centres could warm our homes.”
Short answerYes, in a few places. Across the EU, about 1.8% of it is reused.
Yes, it can, but few do. Practically all the electricity a data centre uses turns into heat. In Odense, Denmark, heat pumps take heat from Meta’s data centre, warm it to 70-75°C and send it into the city’s district heating pipes. The engineers say it heats more than 12,000 homes. A Danish price cap on this kind of heat limited how much the local heat company used, until politicians decided to scrap it. Near Helsinki, Fortum says heat from two Microsoft data centres will start flowing step by step from next year, and once complete should cover about 40% of the 2 TWh a year of district heat used by 250,000 heat users. That’s about 0.8 TWh of heat a year (Hum’s arithmetic). But in the EU’s first reporting round, only 67 of 770 data centres reported reusing any heat, and about 1.8% of all the heat was reused. It needs heat pipes nearby and someone who wants heat, and demand is low in summer and in warm places. EU law now says data centres above 1 MW must use their waste heat unless they show it isn’t technically or economically feasible.
The bigger pictureAll the world’s data centres used about 485 TWh of electricity in 2025, the IEA estimates, and practically all of it ends up as heat. Nobody publishes how much of that is reused worldwide. In the EU, where it is measured, it’s about 1.8%.
Wh is a watt-hour: a 1-watt light left on for an hour. 1 kWh = 1,000 Wh. 1 TWh = 1 billion kWh.
Why the claim misleads
It works, and real homes are heated this way in Odense. But it needs district heating pipes and a cold climate, so most data centres don’t do it: about 1.8% of EU data centres’ heat is reused, and the biggest Nordic scheme hasn’t started taking heat yet.
What nobody knows yet
- Outside the EU, nobody publishes how much data-centre heat is reused.
- The EU’s 1.8% may not be representative: some reported values looked unrealistically high, and some countries with known schemes reported none.
- Only about 36% of the EU data centres that had to report did so in the first round.
- How much Microsoft heat will reach homes near Helsinki, and when, depends on Microsoft’s building schedule.
Sources (15)
- EU Energy Efficiency Directive (EU) 2023/1791, Article 26(6) Rule or law
“Member States shall ensure that data centres with a total rated energy input exceeding 1 MW utilise the waste heat or other waste heat recovery applications unless they can show that it is not technically or economically feasible”
Quote checked on the page, 8 Nov 2026 - European Commission, Report on the energy efficiency of data centres in the EU, COM(2026) 500, September 2026 Estimated
“770 data centres reported their data in the first reporting period, representing around 36% of the estimated total of data centres in the EU falling under the reporting requirement”
Quote checked on the page, 8 Nov 2026 - European Commission, Report on the energy efficiency of data centres in the EU, COM(2026) 500, September 2026 Estimated
“Only 67 data centres reported some waste heat reuse in the first reporting period.”
Quote checked on the page, 8 Nov 2026 - European Commission, Report on the energy efficiency of data centres in the EU, COM(2026) 500, September 2026 Estimated
“approximately 1.8% … of the total heat generated by data centres is being reused in the EU.”
Quote checked on the page, 8 Nov 2026 - European Commission, Report on the energy efficiency of data centres in the EU, COM(2026) 500, September 2026 Estimated
“In the case of data centres, energy reuse focuses on waste heat since practically all electricity consumed by a data centre eventually turns to heat.”
Quote checked on the page, 8 Nov 2026 - European Commission, Report on the energy efficiency of data centres in the EU, COM(2026) 500, September 2026 Estimated
“This figure may not be fully representative of the data centre heat reuse landscape in the EU as some computed values seemed unrealistically high, although they could not be fully falsified. Moreover, although there are known heat reuse projects in some Member States, those same Member States have not reported any data centres on heat reuse.”
Quote checked on the page, 8 Nov 2026 - European Commission, Report on the energy efficiency of data centres in the EU, COM(2026) 500, September 2026 Estimated
“Special attention also needs to be given to climatic and seasonal variations, as demand for heat reuse is lower in warmer climate zones than in colder regions. Even in regions with high heating demand, the seasonality of demand remains a major barrier for high heat reuse rates.”
Quote checked on the page, 8 Nov 2026 - European Commission, Report on the energy efficiency of data centres in the EU, COM(2026) 500, September 2026 Estimated
“waste heat reuse is only possible if there is demand for waste heat from local heat off-takers and local infrastructure for waste heat reuse exists around the facilities”
Quote checked on the page, 8 Nov 2026 - Ramboll (engineers for Fjernvarme Fyn), project page on heat recovery from Meta’s data centre in Odense, Denmark Company says so
“The project, called Tietgenbyen Energy Center, will provide heat to more than 12,000 homes (in 2023), reducing the city's reliance on coal”
Quote checked on the page, 8 Nov 2026 - Ramboll (engineers for Fjernvarme Fyn), project page on heat recovery from Meta’s data centre in Odense, Denmark Company says so
“Here, large electrically driven ammonia heat pumps raise the heat temperature to 70-75°C, suitable for the city's district heating network.”
Quote checked on the page, 8 Nov 2026 - Fjernvarme Fyn (Odense’s district heating company), press release in Danish (17 January 2025) Company says so
“Ind til nu har overskudsvarmen været pålagt et prisloft, der har begrænset Fjernvarme Fyn i deres brug af overskudsvarmen.”
Quote checked on the page, 8 Nov 2026 - Fjernvarme Fyn (Odense’s district heating company), press release in Danish (17 January 2025) Company says so
“Regeringen og Folketingets partier har besluttet at afskaffe prisloftet på overskudsvarme.”
Quote checked on the page, 8 Nov 2026 - Fortum, press release on its heat pump plants at Microsoft’s data centre sites near Helsinki (May 2026) Company says so
“Once fully implemented, data centre waste heat is expected to cover approximately 40 per cent of the total yearly 2 terawatt hour district heat demand of the 250,000 heat users in the area”
Quote checked on the page, 8 Nov 2026 - Fortum, press release on its heat pump plants at Microsoft’s data centre sites near Helsinki (May 2026) Company says so
“The recovery of waste heat from these Microsoft data centre sites will begin step by step next year, in line with Microsoft’s construction and commissioning schedule.”
Quote checked on the page, 8 Nov 2026 - IEA, Key Questions on Energy and AI (2026) Estimated
“electricity consumption from data centres roughly doubling from 485 TWh in 2025 to 950 TWh in 2030”
Quote checked on the page, 3 Oct 2026
Hum’s sums
- 40% of 2 TWh a year = 0.8 TWh of heat a year
Cite this
EU Energy Efficiency Directive (EU) 2023/1791, Article 26(6), as quoted in Hum, “Can the heat from data centres be used to warm homes?”, https://humearth.org/q/heat-reuse (quote checked 8 Nov 2026).
Cite the original source first; Hum is where you found it.
What do Wh, kWh and TWh mean?
Wh is a watt-hour: a 1-watt light left on for an hour. 1 kWh = 1,000 Wh, and 1 TWh = 1 billion kWh. Hum compares each number with something everyday so you don’t need the units.
Send this answer
Can data centres heat homes? Yes: in Odense, Denmark, Meta’s heats more than 12,000 homes, the engineers say. But across the EU only about 1.8% of data centres’ heat is reused.